FR-N1X1G1
Certifications and labels
FR-N1X1G1
This cable is recommended for use in public and industrial settings whenever good fire retardant qualities, reduced fumes, toxic and corrosive gases emissions are required in the case of fire.
Read moreFR-N1X1G1 - 1 x 1,5
Nexans ref.
- Maximum outer diameter: 6.6 mm
- Number of cores: 1
- Conductor cross-section: 1.5 mm²
- Approximate weight: 45 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.09 mm
- Conductor diameter: 1.4 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Perm current rating in air 30°C: 24 A
- Permissible current rating buried 20°C: 31 A
FR-N1X1G1 - 1 x 2,5
Nexans ref.
- Maximum outer diameter: 7.0 mm
- Number of cores: 1
- Conductor cross-section: 2.5 mm²
- Approximate weight: 60 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.09 mm
- Conductor diameter: 1.8 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Perm current rating in air 30°C: 33 A
- Permissible current rating buried 20°C: 41 A
FR-N1X1G1 - 1 x 4
Nexans ref.
- Maximum outer diameter: 7.6 mm
- Number of cores: 1
- Conductor cross-section: 4 mm²
- Approximate weight: 80 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.09 mm
- Conductor diameter: 2.3 mm
- Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
- Perm current rating in air 30°C: 45 A
- Permissible current rating buried 20°C: 53 A
FR-N1X1G1 - 1 x 6
Nexans ref.
- Maximum outer diameter: 8.2 mm
- Number of cores: 1
- Conductor cross-section: 6 mm²
- Approximate weight: 105 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.09 mm
- Conductor diameter: 3.1 mm
- Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
- Perm current rating in air 30°C: 58 A
- Permissible current rating buried 20°C: 66 A
FR-N1X1G1 - 1 x 10
Nexans ref.
- Maximum outer diameter: 9.2 mm
- Number of cores: 1
- Conductor cross-section: 10 mm²
- Approximate weight: 150 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.09 mm
- Conductor diameter: 4.0 mm
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Perm current rating in air 30°C: 80 A
- Permissible current rating buried 20°C: 87 A
FR-N1X1G1 - 1 x 16
Nexans ref.
- Maximum outer diameter: 10.5 mm
- Number of cores: 1
- Conductor cross-section: 16 mm²
- Approximate weight: 220 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.09 mm
- Conductor diameter: 4.8 mm
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Perm current rating in air 30°C: 107 A
- Permissible current rating buried 20°C: 113 A
FR-N1X1G1 - 1 x 25
Nexans ref. 069029113
- Maximum outer diameter: 12.5 mm
- Number of cores: 1
- Conductor cross-section: 25 mm²
- Approximate weight: 325 kg/km
- Average insulation thickness: 0.9 mm
- Average sheath thickness: 1.09 mm
- Conductor diameter: 6.0 mm
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Perm current rating in air 30°C: 138 A
- Permissible current rating buried 20°C: 144 A
FR-N1X1G1 - 1 x 35
Nexans ref. 069031113
- Maximum outer diameter: 13.5 mm
- Number of cores: 1
- Conductor cross-section: 35 mm²
- Approximate weight: 440 kg/km
- Average insulation thickness: 0.9 mm
- Average sheath thickness: 1.09 mm
- Conductor diameter: 7.0 mm
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Perm current rating in air 30°C: 169 A
- Permissible current rating buried 20°C: 174 A
FR-N1X1G1 - 1 x 50
Nexans ref. 069033113
- Maximum outer diameter: 15.0 mm
- Number of cores: 1
- Conductor cross-section: 50 mm²
- Approximate weight: 585 kg/km
- Average insulation thickness: 1.0 mm
- Average sheath thickness: 1.09 mm
- Conductor diameter: 8.1 mm
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Perm current rating in air 30°C: 207 A
- Permissible current rating buried 20°C: 206 A
FR-N1X1G1 - 1 x 70
Nexans ref. 069035113
- Maximum outer diameter: 17.0 mm
- Number of cores: 1
- Conductor cross-section: 70 mm²
- Approximate weight: 805 kg/km
- Average insulation thickness: 1.1 mm
- Average sheath thickness: 1.09 mm
- Conductor diameter: 9.7 mm
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Perm current rating in air 30°C: 268 A
- Permissible current rating buried 20°C: 354 A
FR-N1X1G1 - 1 x 95
Nexans ref. 069037113
- Maximum outer diameter: 19.0 mm
- Number of cores: 1
- Conductor cross-section: 95 mm²
- Approximate weight: 1100 kg/km
- Average insulation thickness: 1.1 mm
- Average sheath thickness: 1.18 mm
- Conductor diameter: 11.4 mm
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Perm current rating in air 30°C: 328 A
- Permissible current rating buried 20°C: 301 A
FR-N1X1G1 - 1 x 120
Nexans ref. 069039113
- Maximum outer diameter: 21.0 mm
- Number of cores: 1
- Conductor cross-section: 120 mm²
- Approximate weight: 1385 kg/km
- Average insulation thickness: 1.2 mm
- Average sheath thickness: 1.18 mm
- Conductor diameter: 13.1 mm
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Perm current rating in air 30°C: 382 A
- Permissible current rating buried 20°C: 343 A
FR-N1X1G1 - 1 x 150
Nexans ref. 069041113
- Maximum outer diameter: 23.0 mm
- Number of cores: 1
- Conductor cross-section: 150 mm²
- Approximate weight: 1700 kg/km
- Average insulation thickness: 1.4 mm
- Average sheath thickness: 1.26 mm
- Conductor diameter: 14.6 mm
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Perm current rating in air 30°C: 441 A
- Permissible current rating buried 20°C: 387 A
FR-N1X1G1 - 1 x 185
Nexans ref. 069043113
- Maximum outer diameter: 25.5 mm
- Number of cores: 1
- Conductor cross-section: 185 mm²
- Approximate weight: 2120 kg/km
- Average insulation thickness: 1.6 mm
- Average sheath thickness: 1.26 mm
- Conductor diameter: 16.5 mm
- Max. DC resistance of the conductor at 20°C: 0.099 Ohm/km
- Perm current rating in air 30°C: 506 A
- Permissible current rating buried 20°C: 434 A
FR-N1X1G1 - 1 x 240
Nexans ref. 069045113
- Maximum outer diameter: 28.5 mm
- Number of cores: 1
- Conductor cross-section: 240 mm²
- Approximate weight: 2910 kg/km
- Average insulation thickness: 1.7 mm
- Average sheath thickness: 1.35 mm
- Conductor diameter: 18.5 mm
- Max. DC resistance of the conductor at 20°C: 0.075 Ohm/km
- Perm current rating in air 30°C: 599 A
- Permissible current rating buried 20°C: 501 A
FR-N1X1G1 - 1 x 300
Nexans ref. 069047113
- Maximum outer diameter: 31.0 mm
- Number of cores: 1
- Conductor cross-section: 300 mm²
- Approximate weight: 3380 kg/km
- Average insulation thickness: 1.8 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 21.0 mm
- Max. DC resistance of the conductor at 20°C: 0.06 Ohm/km
- Perm current rating in air 30°C: 693 A
- Permissible current rating buried 20°C: 565 A
FR-N1X1G1 - 2 x 1,5
Nexans ref. 069069113
- Maximum outer diameter: 10.5 mm
- Number of cores: 2
- Conductor cross-section: 1.5 mm²
- Approximate weight: 130 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.4 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Perm current rating in air 30°C: 26 A
- Permissible current rating buried 20°C: 37 A
FR-N1X1G1 - 2 x 2,5
Nexans ref. 069071113
- Maximum outer diameter: 11.5 mm
- Number of cores: 2
- Conductor cross-section: 2.5 mm²
- Approximate weight: 165 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.8 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Perm current rating in air 30°C: 36 A
- Permissible current rating buried 20°C: 48 A
FR-N1X1G1 - 2 x 4
Nexans ref. 069073113
- Maximum outer diameter: 13.0 mm
- Number of cores: 2
- Conductor cross-section: 4 mm²
- Approximate weight: 200 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 2.3 mm
- Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
- Perm current rating in air 30°C: 49 A
- Permissible current rating buried 20°C: 63 A
FR-N1X1G1 - 2 x 6
Nexans ref. 069075113
- Maximum outer diameter: 14.0 mm
- Number of cores: 2
- Conductor cross-section: 6 mm²
- Approximate weight: 280 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 3.1 mm
- Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
- Perm current rating in air 30°C: 63 A
- Permissible current rating buried 20°C: 80 A
FR-N1X1G1 - 2 x 10
Nexans ref. 069077113
- Maximum outer diameter: 16.0 mm
- Number of cores: 2
- Conductor cross-section: 10 mm²
- Approximate weight: 410 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 4.0 mm
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Perm current rating in air 30°C: 86 A
- Permissible current rating buried 20°C: 104 A
FR-N1X1G1 - 2 x 16
Nexans ref. 069079113
- Maximum outer diameter: 18.5 mm
- Number of cores: 2
- Conductor cross-section: 16 mm²
- Approximate weight: 590 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 4.8 mm
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Perm current rating in air 30°C: 115 A
- Permissible current rating buried 20°C: 136 A
FR-N1X1G1 - 2 x 25
Nexans ref. 069081113
- Maximum outer diameter: 22.0 mm
- Number of cores: 2
- Conductor cross-section: 25 mm²
- Approximate weight: 900 kg/km
- Average insulation thickness: 0.9 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 6.0 mm
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Perm current rating in air 30°C: 149 A
- Permissible current rating buried 20°C: 173 A
FR-N1X1G1 - 2 x 35
Nexans ref. 069083113
- Maximum outer diameter: 24.5 mm
- Number of cores: 2
- Conductor cross-section: 35 mm²
- Approximate weight: 1135 kg/km
- Average insulation thickness: 0.9 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 7.0 mm
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Perm current rating in air 30°C: 185 A
- Permissible current rating buried 20°C: 208 A
FR-N1X1G1 - 3G 1,5
Nexans ref. 069121013
- Maximum outer diameter: 11.0 mm
- Number of cores: 3
- Conductor cross-section: 1.5 mm²
- Approximate weight: 145 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.4 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Perm current rating in air 30°C: 23 A
- Permissible current rating buried 20°C: 31 A
FR-N1X1G1 - 3G 2,5
Nexans ref. 069123013
- Maximum outer diameter: 12.5 mm
- Number of cores: 3
- Conductor cross-section: 2.5 mm²
- Approximate weight: 190 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.8 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Perm current rating in air 30°C: 31 A
- Permissible current rating buried 20°C: 41 A
FR-N1X1G1 - 3G 4
Nexans ref. 069125013
- Maximum outer diameter: 13.5 mm
- Number of cores: 3
- Conductor cross-section: 4 mm²
- Approximate weight: 255 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 2.3 mm
- Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
- Perm current rating in air 30°C: 42 A
- Permissible current rating buried 20°C: 53 A
FR-N1X1G1 - 3G 6
Nexans ref. 069127013
- Maximum outer diameter: 15.0 mm
- Number of cores: 3
- Conductor cross-section: 6 mm²
- Approximate weight: 350 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 3.1 mm
- Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
- Perm current rating in air 30°C: 54 A
- Permissible current rating buried 20°C: 66 A
FR-N1X1G1 - 3G10
Nexans ref. 069129013
- Maximum outer diameter: 17.0 mm
- Number of cores: 3
- Conductor cross-section: 10 mm²
- Approximate weight: 495 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 4.0 mm
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Perm current rating in air 30°C: 75 A
- Permissible current rating buried 20°C: 87 A
FR-N1X1G1 - 3G16
Nexans ref. 069131013
- Maximum outer diameter: 19.5 mm
- Number of cores: 3
- Conductor cross-section: 16 mm²
- Approximate weight: 705 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 4.8 mm
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Perm current rating in air 30°C: 100 A
- Permissible current rating buried 20°C: 113 A
FR-N1X1G1 - 3G25
Nexans ref. 069133013
- Maximum outer diameter: 23.5 mm
- Number of cores: 3
- Conductor cross-section: 25 mm²
- Approximate weight: 1130 kg/km
- Average insulation thickness: 0.9 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 6.0 mm
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Perm current rating in air 30°C: 127 A
- Permissible current rating buried 20°C: 144 A
FR-N1X1G1 - 3G35
Nexans ref. 069135013
- Maximum outer diameter: 26.0 mm
- Number of cores: 3
- Conductor cross-section: 35 mm²
- Approximate weight: 1510 kg/km
- Average insulation thickness: 0.9 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 7.0 mm
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Perm current rating in air 30°C: 158 A
- Permissible current rating buried 20°C: 174 A
FR-N1X1G1 - 3G50
Nexans ref. 069137013
- Maximum outer diameter: 29.0 mm
- Number of cores: 3
- Conductor cross-section: 50 mm²
- Approximate weight: 1985 kg/km
- Average insulation thickness: 1.0 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 8.1 mm
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Perm current rating in air 30°C: 192 A
- Permissible current rating buried 20°C: 206 A
FR-N1X1G1 - 3G70
Nexans ref. 069139013
- Maximum outer diameter: 34.0 mm
- Number of cores: 3
- Conductor cross-section: 70 mm²
- Approximate weight: 2770 kg/km
- Average insulation thickness: 1.1 mm
- Average sheath thickness: 1.52 mm
- Conductor diameter: 9.7 mm
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Perm current rating in air 30°C: 246 A
- Permissible current rating buried 20°C: 254 A
FR-N1X1G1 - 3G95
Nexans ref.
- Maximum outer diameter: 38.5 mm
- Number of cores: 3
- Conductor cross-section: 95 mm²
- Approximate weight: 3790 kg/km
- Average insulation thickness: 1.1 mm
- Average sheath thickness: 1.6 mm
- Conductor diameter: 11.4 mm
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Perm current rating in air 30°C: 298 A
- Permissible current rating buried 20°C: 301 A
FR-N1X1G1 - 3 x 120
Nexans ref.
- Maximum outer diameter: 42.5 mm
- Number of cores: 3
- Conductor cross-section: 120 mm²
- Approximate weight: 4810 kg/km
- Average insulation thickness: 1.2 mm
- Average sheath thickness: 1.69 mm
- Conductor diameter: 13.1 mm
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Perm current rating in air 30°C: 346 A
- Permissible current rating buried 20°C: 343 A
FR-N1X1G1 - 3 x 150
Nexans ref.
- Maximum outer diameter: 47.5 mm
- Number of cores: 3
- Conductor cross-section: 150 mm²
- Approximate weight: 5935 kg/km
- Average insulation thickness: 1.4 mm
- Average sheath thickness: 1.86 mm
- Conductor diameter: 14.6 mm
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Perm current rating in air 30°C: 395 A
- Permissible current rating buried 20°C: 387 A
FR-N1X1G1 - 3 x 185
Nexans ref.
- Maximum outer diameter: 53.0 mm
- Number of cores: 3
- Conductor cross-section: 185 mm²
- Approximate weight: 7460 kg/km
- Average insulation thickness: 1.6 mm
- Average sheath thickness: 1.94 mm
- Conductor diameter: 16.5 mm
- Max. DC resistance of the conductor at 20°C: 0.099 Ohm/km
- Perm current rating in air 30°C: 450 A
- Permissible current rating buried 20°C: 434 A
FR-N1X1G1 - 3 x 240
Nexans ref.
- Maximum outer diameter: 59.5 mm
- Number of cores: 3
- Conductor cross-section: 240 mm²
- Approximate weight: 9510 kg/km
- Average insulation thickness: 1.7 mm
- Average sheath thickness: 2.11 mm
- Conductor diameter: 18.5 mm
- Max. DC resistance of the conductor at 20°C: 0.075 Ohm/km
- Perm current rating in air 30°C: 538 A
- Permissible current rating buried 20°C: 501 A
FR-N1X1G1 - 3 x 300
Nexans ref.
- Maximum outer diameter: 66.0 mm
- Number of cores: 3
- Conductor cross-section: 300 mm²
- Approximate weight: 12100 kg/km
- Average insulation thickness: 1.8 mm
- Average sheath thickness: 2.28 mm
- Conductor diameter: 21.0 mm
- Max. DC resistance of the conductor at 20°C: 0.06 Ohm/km
- Perm current rating in air 30°C: 621 A
- Permissible current rating buried 20°C: 565 A
FR-N1X1G1 - 4G1,5
Nexans ref. 069173013
- Maximum outer diameter: 12.0 mm
- Number of cores: 4
- Conductor cross-section: 1.5 mm²
- Approximate weight: 170 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.4 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Perm current rating in air 30°C: 23 A
- Permissible current rating buried 20°C: 31 A
FR-N1X1G1 - 4G 2,5
Nexans ref. 069175013
- Maximum outer diameter: 13.0 mm
- Number of cores: 4
- Conductor cross-section: 2.5 mm²
- Approximate weight: 225 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.8 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Perm current rating in air 30°C: 31 A
- Permissible current rating buried 20°C: 41 A
FR-N1X1G1 - 4G4
Nexans ref. 069177013
- Maximum outer diameter: 14.5 mm
- Number of cores: 4
- Conductor cross-section: 4 mm²
- Approximate weight: 305 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 2.3 mm
- Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
- Perm current rating in air 30°C: 42 A
- Permissible current rating buried 20°C: 53 A
FR-N1X1G1 - 4G 6
Nexans ref. 069179013
- Maximum outer diameter: 16.0 mm
- Number of cores: 4
- Conductor cross-section: 6 mm²
- Approximate weight: 420 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 3.1 mm
- Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
- Perm current rating in air 30°C: 54 A
- Permissible current rating buried 20°C: 66 A
FR-N1X1G1 - 4G10
Nexans ref. 069181013
- Maximum outer diameter: 18.5 mm
- Number of cores: 4
- Conductor cross-section: 10 mm²
- Approximate weight: 610 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 4.0 mm
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Perm current rating in air 30°C: 75 A
- Permissible current rating buried 20°C: 87 A
FR-N1X1G1 - 4G16
Nexans ref. 069183013
- Maximum outer diameter: 21.0 mm
- Number of cores: 4
- Conductor cross-section: 16 mm²
- Approximate weight: 870 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 4.8 mm
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Perm current rating in air 30°C: 100 A
- Permissible current rating buried 20°C: 113 A
FR-N1X1G1 - 4G25
Nexans ref. 069185013
- Maximum outer diameter: 25.5 mm
- Number of cores: 4
- Conductor cross-section: 25 mm²
- Approximate weight: 1350 kg/km
- Average insulation thickness: 0.9 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 6.0 mm
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Perm current rating in air 30°C: 127 A
- Permissible current rating buried 20°C: 144 A
FR-N1X1G1 - 4G35
Nexans ref. 069187013
- Maximum outer diameter: 28.5 mm
- Number of cores: 4
- Conductor cross-section: 35 mm²
- Approximate weight: 1895 kg/km
- Average insulation thickness: 0.9 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 7.0 mm
- Max. DC resistance of the conductor at 20°C: 0.524 Ohm/km
- Perm current rating in air 30°C: 158 A
- Permissible current rating buried 20°C: 174 A
FR-N1X1G1 - 4G50
Nexans ref. 069189013
- Maximum outer diameter: 32.5 mm
- Number of cores: 4
- Conductor cross-section: 50 mm²
- Approximate weight: 2510 kg/km
- Average insulation thickness: 1.0 mm
- Average sheath thickness: 1.52 mm
- Conductor diameter: 8.1 mm
- Max. DC resistance of the conductor at 20°C: 0.387 Ohm/km
- Perm current rating in air 30°C: 192 A
- Permissible current rating buried 20°C: 206 A
FR-N1X1G1 - 4G70
Nexans ref. 069191013
- Maximum outer diameter: 37.5 mm
- Number of cores: 4
- Conductor cross-section: 70 mm²
- Approximate weight: 3545 kg/km
- Average insulation thickness: 1.1 mm
- Average sheath thickness: 1.6 mm
- Conductor diameter: 9.7 mm
- Max. DC resistance of the conductor at 20°C: 0.268 Ohm/km
- Perm current rating in air 30°C: 246 A
- Permissible current rating buried 20°C: 254 A
FR-N1X1G1 - 4G95
Nexans ref. 069193013
- Maximum outer diameter: 42.5 mm
- Number of cores: 4
- Conductor cross-section: 95 mm²
- Approximate weight: 4835 kg/km
- Average insulation thickness: 1.1 mm
- Average sheath thickness: 1.69 mm
- Conductor diameter: 11.4 mm
- Max. DC resistance of the conductor at 20°C: 0.193 Ohm/km
- Perm current rating in air 30°C: 298 A
- Permissible current rating buried 20°C: 301 A
FR-N1X1G1 - 4 x 120
Nexans ref.
- Maximum outer diameter: 47.5 mm
- Number of cores: 4
- Conductor cross-section: 120 mm²
- Approximate weight: 6130 kg/km
- Average insulation thickness: 1.2 mm
- Average sheath thickness: 1.86 mm
- Conductor diameter: 13.1 mm
- Max. DC resistance of the conductor at 20°C: 0.153 Ohm/km
- Perm current rating in air 30°C: 346 A
- Permissible current rating buried 20°C: 343 A
FR-N1X1G1 - 4 x 150
Nexans ref.
- Maximum outer diameter: 52.5 mm
- Number of cores: 4
- Conductor cross-section: 150 mm²
- Approximate weight: 7530 kg/km
- Average insulation thickness: 1.4 mm
- Average sheath thickness: 1.94 mm
- Conductor diameter: 14.6 mm
- Max. DC resistance of the conductor at 20°C: 0.124 Ohm/km
- Perm current rating in air 30°C: 395 A
- Permissible current rating buried 20°C: 387 A
FR-N1X1G1 - 4 x 185
Nexans ref.
- Maximum outer diameter: 59.0 mm
- Number of cores: 4
- Conductor cross-section: 185 mm²
- Approximate weight: 9710 kg/km
- Average insulation thickness: 1.6 mm
- Average sheath thickness: 2.11 mm
- Conductor diameter: 16.5 mm
- Max. DC resistance of the conductor at 20°C: 0.099 Ohm/km
- Perm current rating in air 30°C: 450 A
- Permissible current rating buried 20°C: 434 A
FR-N1X1G1 - 4 x 240
Nexans ref.
- Maximum outer diameter: 66.5 mm
- Number of cores: 4
- Conductor cross-section: 240 mm²
- Approximate weight: 12350 kg/km
- Average insulation thickness: 1.7 mm
- Average sheath thickness: 2.28 mm
- Conductor diameter: 18.5 mm
- Max. DC resistance of the conductor at 20°C: 0.075 Ohm/km
- Perm current rating in air 30°C: 538 A
- Permissible current rating buried 20°C: 501 A
FR-N1X1G1 - 4 x 300
Nexans ref.
- Maximum outer diameter: 73.5 mm
- Number of cores: 4
- Conductor cross-section: 300 mm²
- Approximate weight: 15950 kg/km
- Average insulation thickness: 1.8 mm
- Average sheath thickness: 2.45 mm
- Conductor diameter: 21.0 mm
- Max. DC resistance of the conductor at 20°C: 0.06 Ohm/km
- Perm current rating in air 30°C: 621 A
- Permissible current rating buried 20°C: 565 A
FR-N1X1G1 - 5G1,5
Nexans ref. 069225013
- Maximum outer diameter: 13.0 mm
- Number of cores: 5
- Conductor cross-section: 1.5 mm²
- Approximate weight: 200 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.4 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Perm current rating in air 30°C: 23 A
- Permissible current rating buried 20°C: 31 A
FR-N1X1G1 - 5G2,5
Nexans ref. 069227013
- Maximum outer diameter: 14.5 mm
- Number of cores: 5
- Conductor cross-section: 2.5 mm²
- Approximate weight: 265 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.8 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Perm current rating in air 30°C: 31 A
- Permissible current rating buried 20°C: 41 A
FR-N1X1G1 - 5G 4
Nexans ref. 069229013
- Maximum outer diameter: 16.0 mm
- Number of cores: 5
- Conductor cross-section: 4 mm²
- Approximate weight: 365 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 2.3 mm
- Max. DC resistance of the conductor at 20°C: 4.61 Ohm/km
- Perm current rating in air 30°C: 42 A
- Permissible current rating buried 20°C: 53 A
FR-N1X1G1 - 5G 6
Nexans ref. 069231013
- Maximum outer diameter: 17.5 mm
- Number of cores: 5
- Conductor cross-section: 6 mm²
- Approximate weight: 505 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 3.1 mm
- Max. DC resistance of the conductor at 20°C: 3.08 Ohm/km
- Perm current rating in air 30°C: 54 A
- Permissible current rating buried 20°C: 66 A
FR-N1X1G1 - 5G10
Nexans ref. 069233013
- Maximum outer diameter: 20.0 mm
- Number of cores: 5
- Conductor cross-section: 10 mm²
- Approximate weight: 740 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 4.0 mm
- Max. DC resistance of the conductor at 20°C: 1.83 Ohm/km
- Perm current rating in air 30°C: 75 A
- Permissible current rating buried 20°C: 87 A
FR-N1X1G1 - 5G16
Nexans ref. 069235013
- Maximum outer diameter: 23.0 mm
- Number of cores: 5
- Conductor cross-section: 16 mm²
- Approximate weight: 1065 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 4.8 mm
- Max. DC resistance of the conductor at 20°C: 1.15 Ohm/km
- Perm current rating in air 30°C: 100 A
- Permissible current rating buried 20°C: 113 A
FR-N1X1G1 - 5G25
Nexans ref. 069237013
- Maximum outer diameter: 28.0 mm
- Number of cores: 5
- Conductor cross-section: 25 mm²
- Approximate weight: 1645 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 4.8 mm
- Max. DC resistance of the conductor at 20°C: 0.727 Ohm/km
- Perm current rating in air 30°C: 127 A
- Permissible current rating buried 20°C: 144 A
FR-N1X1G1 - 7G1,5
Nexans ref. 069301013
- Maximum outer diameter: 13.5 mm
- Number of cores: 7
- Conductor cross-section: 1.5 mm²
- Approximate weight: 245 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.4 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Perm current rating in air 30°C: 15 A
- Permissible current rating buried 20°C: 22 A
FR-N1X1G1 - 7G2,5
Nexans ref. 069303013
- Maximum outer diameter: 15.0 mm
- Number of cores: 7
- Conductor cross-section: 2.5 mm²
- Approximate weight: 330 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.8 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Perm current rating in air 30°C: 20 A
- Permissible current rating buried 20°C: 28 A
FR-N1X1G1 - 8 x 1,5
Nexans ref.
- Maximum outer diameter: 14.5 mm
- Number of cores: 8
- Conductor cross-section: 1.5 mm²
- Approximate weight: 265 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.4 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Perm current rating in air 30°C: 14 A
- Permissible current rating buried 20°C: 20 A
FR-N1X1G1 - 8 x 2,5
Nexans ref.
- Maximum outer diameter: 16.5 mm
- Number of cores: 8
- Conductor cross-section: 2.5 mm²
- Approximate weight: 370 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.8 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Perm current rating in air 30°C: 19 A
- Permissible current rating buried 20°C: 27 A
FR-N1X1G1 - 12G1,5
Nexans ref. 069373013
- Maximum outer diameter: 17.0 mm
- Number of cores: 12
- Conductor cross-section: 1.5 mm²
- Approximate weight: 385 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.4 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Perm current rating in air 30°C: 12 A
- Permissible current rating buried 20°C: 18 A
FR-N1X1G1 - 12G2,5
Nexans ref. 069375013
- Maximum outer diameter: 19.5 mm
- Number of cores: 12
- Conductor cross-section: 2.5 mm²
- Approximate weight: 550 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.8 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Perm current rating in air 30°C: 17 A
- Permissible current rating buried 20°C: 24 A
FR-N1X1G1 - 19G1,5
Nexans ref. 069469013
- Maximum outer diameter: 19.5 mm
- Number of cores: 19
- Conductor cross-section: 1.5 mm²
- Approximate weight: 545 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.4 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Perm current rating in air 30°C: 10 A
- Permissible current rating buried 20°C: 15 A
FR-N1X1G1 - 19G2,5
Nexans ref. 069471013
- Maximum outer diameter: 22.5 mm
- Number of cores: 19
- Conductor cross-section: 2.5 mm²
- Approximate weight: 785 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.8 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Perm current rating in air 30°C: 14 A
- Permissible current rating buried 20°C: 20 A
FR-N1X1G1 - 24 x 1,5
Nexans ref.
- Maximum outer diameter: 22.5 mm
- Number of cores: 24
- Conductor cross-section: 1.5 mm²
- Approximate weight: 750 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.4 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Perm current rating in air 30°C: 10 A
- Permissible current rating buried 20°C: 14 A
FR-N1X1G1 - 24 x 2,5
Nexans ref.
- Maximum outer diameter: 25.5 mm
- Number of cores: 24
- Conductor cross-section: 2.5 mm²
- Approximate weight: 1050 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.8 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Perm current rating in air 30°C: 13 A
- Permissible current rating buried 20°C: 18 A
FR-N1X1G1 - 27 x 1,5
Nexans ref.
- Maximum outer diameter: 23.0 mm
- Number of cores: 27
- Conductor cross-section: 1.5 mm²
- Approximate weight: 850 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.4 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Perm current rating in air 30°C: 9 A
- Permissible current rating buried 20°C: 12 A
FR-N1X1G1 - 27 x 2,5
Nexans ref.
- Maximum outer diameter: 27.0 mm
- Number of cores: 27
- Conductor cross-section: 2.5 mm²
- Approximate weight: 1190 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.8 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Perm current rating in air 30°C: 12 A
- Permissible current rating buried 20°C: 16 A
FR-N1X1G1 - 37 x 1,5
Nexans ref.
- Maximum outer diameter: 25.5 mm
- Number of cores: 37
- Conductor cross-section: 1.5 mm²
- Approximate weight: 1010 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.4 mm
- Max. DC resistance of the conductor at 20°C: 12.1 Ohm/km
- Perm current rating in air 30°C: 8 A
- Permissible current rating buried 20°C: 12 A
FR-N1X1G1 - 37 x 2,5
Nexans ref.
- Maximum outer diameter: 29.5 mm
- Number of cores: 37
- Conductor cross-section: 2.5 mm²
- Approximate weight: 1460 kg/km
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.43 mm
- Conductor diameter: 1.8 mm
- Max. DC resistance of the conductor at 20°C: 7.41 Ohm/km
- Perm current rating in air 30°C: 11 A
- Permissible current rating buried 20°C: 16 A
Description
Description
Standards
-
ProductIEC 60228; NF C32-323
Use and installation method
This cable is recommended for use in public and industrial settings whenever good fire retardant qualities, reduced fumes, toxic and corrosive gases emissions are required in the case of fire. For use in industrial settings, in the upright columns of buildings when strict safety standards have to be respected. It offers good resistance to low temperatures, chemical agents, solar radiation, and mechanical forces in general. Can be used for static applications in the open air, in pipes, or in cable trenches. The cable can be laid directly in the ground for short periods on the condition that the ground is not flooded and that it is provided with suitable mechanical protection. With appropriate mechanical protection, it can be used in areas subject to the risk of explosion, but in this case the permitted current load is reduced by 15%.
Installation conditions
- Minimum installation temperature: 0°C
- Recommended minimum bending radius: 12 times the cable diameter
- Recommended maximum tensile stress: 50 N/mm² of the cross-section of the copper
Construction
- Conductor:
- plain copper, solid, class 1 (cross-section ≤ 4mm2)
- plain copper, stranded wire, class 2 (cross-section ≥ 6mm2)
- Insulation: XLPE (cross-linked polyethylene)
- Filler: LS0H thermoplastic
- Sheath: LS0H polyolefin
- Colour: green
LS0H = Low Smoke Zero Halogen
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Documentation
Selling & delivery Information
Marking
”TRISECUR” NF-USE 337 FR-N1X1G1-U/R 0,6/1 kV Cca-s1,d1,a1 [form.] NF C 32-323 [anno] [ordine] [metrica]
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania