Suitable for the transport of power in the industry, construction sites and housing. For static use outdoor and indoor, in brickwork, metal structures, gangways, pipes, ducts or similar closed systems. Allowed for underground laying also unprotected.
Read moreARG16M16-0,6/1 kV 1 x 120
Nexans ref. 617039113
- Construction type: 1 x 120
- Conductor cross-section: 120 mm²
- Conductor diameter: 12.9 mm
- Average insulation thickness: 1.2 mm
- Average sheath thickness: 1.5 mm
- Approximate weight: 525 kg/km
- Maximum outer diameter: 22.0 mm
- Max. DC resistance of the conductor at 20°C: 0.253 Ohm/km
- Perm current rating in air 30°C: 310 A
- Perm. current rating in pipe/air 30° C: 250 A
- Perm. current rating in pipe/buried 20° C: 238 A
- Permissible current rating buried/direct 20°C: 277 A
ARG16M16-0,6/1 kV 1 x 150
Nexans ref. 617041113
- Construction type: 1 x 150
- Conductor cross-section: 150 mm²
- Conductor diameter: 14.2 mm
- Average insulation thickness: 1.4 mm
- Average sheath thickness: 1.6 mm
- Approximate weight: 630 kg/km
- Maximum outer diameter: 24.3 mm
- Max. DC resistance of the conductor at 20°C: 0.206 Ohm/km
- Perm current rating in air 30°C: 350 A
- Perm. current rating in pipe/air 30° C: 280 A
- Perm. current rating in pipe/buried 20° C: 250 A
- Permissible current rating buried/direct 20°C: 313 A
ARG16M16-0,6/1 kV 1 x 16
Nexans ref. 617027113
- Construction type: 1 x 16
- Conductor cross-section: 16 mm²
- Conductor diameter: 4.9 mm
- Average insulation thickness: 0.7 mm
- Average sheath thickness: 1.4 mm
- Approximate weight: 125 kg/km
- Maximum outer diameter: 12.5 mm
- Max. DC resistance of the conductor at 20°C: 1.91 Ohm/km
- Perm current rating in air 30°C: 70 A
- Perm. current rating in pipe/air 30° C: 64 A
- Perm. current rating in pipe/buried 20° C: 75 A
- Permissible current rating buried/direct 20°C: 98 A
ARG16M16-0,6/1 kV 1 x 185
Nexans ref. 617043113
- Construction type: 1 x 185
- Conductor cross-section: 185 mm²
- Conductor diameter: 16.0 mm
- Average insulation thickness: 1.6 mm
- Average sheath thickness: 1.6 mm
- Approximate weight: 785 kg/km
- Maximum outer diameter: 26.7 mm
- Max. DC resistance of the conductor at 20°C: 0.164 Ohm/km
- Perm current rating in air 30°C: 415 A
- Perm. current rating in pipe/air 30° C: 334 A
- Perm. current rating in pipe/buried 20° C: 300 A
- Permissible current rating buried/direct 20°C: 350 A
ARG16M16-0,6/1 kV 1 x 240
Nexans ref. 617045113
- Construction type: 1 x 240
- Conductor cross-section: 240 mm²
- Conductor diameter: 18.4 mm
- Average insulation thickness: 1.7 mm
- Average sheath thickness: 1.7 mm
- Approximate weight: 985 kg/km
- Maximum outer diameter: 29.6 mm
- Max. DC resistance of the conductor at 20°C: 0.125 Ohm/km
- Perm current rating in air 30°C: 490 A
- Perm. current rating in pipe/air 30° C: 392 A
- Perm. current rating in pipe/buried 20° C: 331 A
- Permissible current rating buried/direct 20°C: 413 A
ARG16M16-0,6/1 kV 1 x 25
Nexans ref. 617029113
- Construction type: 1 x 25
- Conductor cross-section: 25 mm²
- Conductor diameter: 6.1 mm
- Average insulation thickness: 0.9 mm
- Average sheath thickness: 1.4 mm
- Approximate weight: 165 kg/km
- Maximum outer diameter: 13.7 mm
- Max. DC resistance of the conductor at 20°C: 1.2 Ohm/km
- Perm current rating in air 30°C: 102 A
- Perm. current rating in pipe/air 30° C: 88 A
- Perm. current rating in pipe/buried 20° C: 95 A
- Permissible current rating buried/direct 20°C: 119 A
ARG16M16-0,6/1 kV 1 x 300
Nexans ref. 617047113
- Construction type: 1 x 300
- Conductor cross-section: 300 mm²
- Conductor diameter: 20.5 mm
- Average insulation thickness: 1.8 mm
- Average sheath thickness: 1.8 mm
- Approximate weight: 1225 kg/km
- Maximum outer diameter: 32.2 mm
- Max. DC resistance of the conductor at 20°C: 0.1 Ohm/km
- Perm current rating in air 30°C: 567 A
- Perm. current rating in pipe/air 30° C: - A
- Perm. current rating in pipe/buried 20° C: 400 A
- Permissible current rating buried/direct 20°C: 454 A
ARG16M16-0,6/1 kV 1 x 35
Nexans ref. 617031113
- Construction type: 1 x 35
- Conductor cross-section: 35 mm²
- Conductor diameter: 7.1 mm
- Average insulation thickness: 0.9 mm
- Average sheath thickness: 1.4 mm
- Approximate weight: 202 kg/km
- Maximum outer diameter: 15.0 mm
- Max. DC resistance of the conductor at 20°C: 0.868 Ohm/km
- Perm current rating in air 30°C: 136 A
- Perm. current rating in pipe/air 30° C: 110 A
- Perm. current rating in pipe/buried 20° C: 115 A
- Permissible current rating buried/direct 20°C: 141 A
ARG16M16-0,6/1 kV 1 x 400
Nexans ref. 617049113
- Construction type: 1 x 400
- Conductor cross-section: 400 mm²
- Conductor diameter: 23.6 mm
- Average insulation thickness: 2.0 mm
- Average sheath thickness: 1.9 mm
- Approximate weight: 1540 kg/km
- Maximum outer diameter: 36.7 mm
- Max. DC resistance of the conductor at 20°C: 0.078 Ohm/km
- Perm current rating in air 30°C: 665 A
- Perm. current rating in pipe/air 30° C: - A
- Perm. current rating in pipe/buried 20° C: 450 A
- Permissible current rating buried/direct 20°C: 512 A
ARG16M16-0,6/1 kV 1 x 50
Nexans ref. 617033113
- Construction type: 1 x 50
- Conductor cross-section: 50 mm²
- Conductor diameter: 8.2 mm
- Average insulation thickness: 1.0 mm
- Average sheath thickness: 1.4 mm
- Approximate weight: 250 kg/km
- Maximum outer diameter: 16.2 mm
- Max. DC resistance of the conductor at 20°C: 0.641 Ohm/km
- Perm current rating in air 30°C: 164 A
- Perm. current rating in pipe/air 30° C: 131 A
- Perm. current rating in pipe/buried 20° C: 134 A
- Permissible current rating buried/direct 20°C: 167 A
ARG16M16-0,6/1 kV 1 x 500
Nexans ref. 617051113
- Construction type: 1 x 500
- Conductor cross-section: 500 mm²
- Conductor diameter: 26.5 mm
- Average insulation thickness: 2.2 mm
- Average sheath thickness: 2.0 mm
- Approximate weight: 1970 kg/km
- Maximum outer diameter: 40.3 mm
- Max. DC resistance of the conductor at 20°C: 0.06 Ohm/km
- Perm current rating in air 30°C: 765 A
- Perm. current rating in pipe/air 30° C: - A
- Perm. current rating in pipe/buried 20° C: 505 A
- Permissible current rating buried/direct 20°C: 578 A
ARG16M16-0,6/1 kV 1 x 630
Nexans ref. 617052113
- Construction type: 1 x 630
- Conductor cross-section: 600 mm²
- Conductor diameter: 30.1 mm
- Average insulation thickness: 2.4 mm
- Average sheath thickness: 2.2 mm
- Approximate weight: 2460 kg/km
- Maximum outer diameter: 44.6 mm
- Max. DC resistance of the conductor at 20°C: 0.047 Ohm/km
- Perm current rating in air 30°C: 880 A
- Perm. current rating in pipe/air 30° C: - A
- Perm. current rating in pipe/buried 20° C: 580 A
- Permissible current rating buried/direct 20°C: 646 A
ARG16M16-0,6/1 kV 1 x 70
Nexans ref. 617035113
- Construction type: 1 x 70
- Conductor cross-section: 70 mm²
- Conductor diameter: 9.8 mm
- Average insulation thickness: 1.1 mm
- Average sheath thickness: 1.4 mm
- Approximate weight: 330 kg/km
- Maximum outer diameter: 18.1 mm
- Max. DC resistance of the conductor at 20°C: 0.443 Ohm/km
- Perm current rating in air 30°C: 218 A
- Perm. current rating in pipe/air 30° C: 175 A
- Perm. current rating in pipe/buried 20° C: 173 A
- Permissible current rating buried/direct 20°C: 204 A
ARG16M16-0,6/1 kV 1 x 95
Nexans ref. 617037113
- Construction type: 1 x 95
- Conductor cross-section: 95 mm²
- Conductor diameter: 11.4 mm
- Average insulation thickness: 1.1 mm
- Average sheath thickness: 1.5 mm
- Approximate weight: 430 kg/km
- Maximum outer diameter: 20.1 mm
- Max. DC resistance of the conductor at 20°C: 0.32 Ohm/km
- Perm current rating in air 30°C: 261 A
- Perm. current rating in pipe/air 30° C: 209 A
- Perm. current rating in pipe/buried 20° C: 196 A
- Permissible current rating buried/direct 20°C: 245 A
Description
Description
Standards
-
ProductCEI 20-13; CEI-UNEL 35396; LVD 2014/35/EU
-
TestCEI 20-38
-
InternationalEU Directive 2011/65/EU (RoHS)
Use and installation methods
Reference CEI 20-67 Guide:
Power cables suitable for limiting the spread of fire, the production and diffusion of opaque fumes and acid gases.
Suitable for bundle installations in environments with a higher risk of fire or high occupancy, long evacuation times or high risk of damage to animals and property, such as healthcare facilities (CEI 64-56), public entertainment venues, shopping centres and hotels. Suitable for indoor or outdoor use, even in wet environments, for fixed installation in free air, pipes or ducts, on masonry and metal structures or suspended.
Reference Construction Products Regulation 305/2011 EU and Standard EN 50575:
Given its properties of limiting the spread of fire and harmful fumes, the cable is suitable for supplying electrical power in buildings and other civil engineering works.
Special features
Good resistance to industrial oils and greases. Good performance at low temperatures.
Installation conditions
- Minimum installation temperature: 0°C
- Recommended minimum bending radius: 12 times the cable diameter
- Recommended maximum tensile stress: 50 N/mm² of the cross-section of the conductor
Construction
- Conductor: aluminum, stranded wire, class 2
- Insulation: rubber compound, G16 quality
- Sheath: thermoplastic LS0H, M16 quality
- Colour: green
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Documentation
Selling & delivery Information
Marking
Made in Italy LA TRIVENETA CAVI ARG16M16 0,6/1 kV [form.] Cca-s1b,d1,a1 IEMMEQU EFP [anno] [ordine] [metrica]
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania